Plan reviewed with PENDING comment for revision to remove a fire wall. Reviewed using FFPC 5th edition.

Reviewer: Sandra Boike 904 209 1741  sboike@sjcfl.us
Victoria Vitori 904 209 1748 vvitori@sjcfl.us 

To schedule fire inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

--------------------------------------

Thursday, June 01, 2017

APPROVED for new pages A1, A2, A2.1, & A5

* Revision to remove fire rated partition.

6/1/2017 sboike

This revision does not give information in NFPA 101:6 for mixed occupancy. The space was originally reviewed as a separated occupancy. Mixed occupancy will change the review. If the fire dampers are going to be removed this will no longer be a fire wall.  Please provide information stating that the current mixed occupancy complies with all occupancies in the building Per NFPA 101:6 mixed occupancy. Letter from an architect (signed and sealed) can be sent in when the plans are resubmitted.

---------------------------------------------------

Thursday, June 01, 2017

Reference provided for this allowance to remove the 1 hour separation between the office and the service area. Reference is for NFPA 101: 6.1.14.1.3. Exception 2 Also, reference NFPA 1:12.9.5.3.  

6/1/2017 sboike