Clearance Sheet C2016-006384

 Department IssuesSigned OffIntl

Plan reviewed with PENDING comment for revision to remove a fire wall. Reviewed using FFPC 5th edition.

Reviewer: Sandra Boike 904 209 1741  sboike@sjcfl.us
Victoria Vitori 904 209 1748 vvitori@sjcfl.us 

To schedule fire inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

This revision does not give information in NFPA 101:6 for mixed occupancy. The space was originally reviewed as a separated occupancy. Mixed occupancy will change the review. If the fire dampers are going to be removed this will no longer be a fire wall.  Please provide information stating that the current mixed occupancy complies with all occupancies in the building Per NFPA 101:6 mixed occupancy. Letter from an architect (signed and sealed) can be sent in when the plans are resubmitted.