Clearance Sheet C2016-006384

 Department IssuesSigned OffIntl

Plan reviewed with NO PENDING comments for new dry system with 84 heads. Reviewed using FFPC 5th edition.

Reviewer: Sandra Boike 904 209 1741  sboike@sjcfl.us

To reply to comments and/or resubmit plans, contact your permit tech via email or call 904-827-6800. To help speed the review process you may include a written comment response summary to clarify or illustrate where corrections were made on plans.  Please remember to use the Florida Fire Prevention Code 5th Ed for all code reference in a response to comments. The fire plans examiner does not use or have a copy of the Florida Building Code. You are required to remove old pages and reinsert the new pages.

Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the FFPC 5th ed.

3/15/2017 sboike

Do not forget to:

- include hydraulic design information sign AND general information sign at riser. NFPA 13 Ch24.

- ID control, drain, and test connection valves with a weatherproof metal or rigid plastic sign. NFPA 13 6.7.4

- include a stock of spare sprinklers in a cabinet on premises in an area not to exceed 100 degrees WITH a wrench for each type of sprinkler installed or to be used. NFPA 13 6.2.9

- a list of the sprinklers installed in the property shall be posted in the sprinkler cabinet. It shall include: 1) SIN or manufacturer, model, orifice, deflector type, thermal sensitivity, and pressure rating  2) general description  3) quantity of each type to be contained in cabinet  4) Issue or revision date of list. NFPA 13 6.2.9.7

3/15/2017 sboike