Plan reviewed with PENDING comments for new fire sprinkler system. Reviewed using FFPC 5th edition.

Reviewer: Sandra Boike 904 209 1741  sboike@sjcfl.us

To reply to comments and/or resubmit plans, contact your permit tech via email or call 904-827-6800. To help speed the review process you may include a written comment response summary to clarify or illustrate where corrections were made on plans.  Please remember to use the Florida Fire Prevention Code 5th Ed for all code reference in a response to comments. The fire plans examiner does not use or have a copy of the Florida Building Code. You are required to remove old pages and reinsert the new pages.

Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the FFPC 5th ed.

 

Florida Administrative Code (FAC) 61G15-32.002 defines a material deviation as "Any deviation from the design parameters established and documented by the Engineer of Record." Furthermore FAC 61G15-32.003(6) states "When layout documents contain material deviation from the Engineer of Record's Fire Protection System Engineering Document, such layout documents are not compliant unless they are accompanied by revised Engineering Documents made and sealed by the Engineer of record for the Fire Protection System."

 

The deisgn criteria from Hinkle stated wet pipe system and dry pipe system for this building.

1) either contact Hinkle to revise the 61G criteria for dry system only.

OR

2) Resubmit shop drawings to follow the design criteria.

 

Review has stopped until issue with design and shop drawings has been resolved.