Clearance Sheet C2016-006384

 Department IssuesSigned OffIntl

Plan REJECTED as a 9393sf Special Use Industrial (NFPA 101) Repair Garage (NFPA 1). Reviewed using the Florida Fire Prevention Code 5th ED.

 

Rejected need clearance sheet.  


Friday, December 30, 2016

c16-6384

12/30/2016 sboike

NFPA 1.30.2.5.1 Are the floors going to be liquid tight. Information/ data sheets needed on the product being used.


Friday, December 30, 2016

Response: yes, service floors will be sealed with Ashford sealer/hardener. Please refer to revised sheets A1&A8 for approval.

12/30/2016 sboike

NFPA 1.2.5.2 Please provide more information about floor drains used.


Friday, December 30, 2016

Response: The floor drain is exclusively in wash bay for washing company trucks. All discharge from drain will go to grease interceptor shown on sheet P1. Please review for approval.

12/30/2016 sboike

NFPA 1.30.2.7(1) The building height is stated on sheet A3 as 36 feet in height. This appears to meet the requirement for major repair garage over two stories in height requiring a fire sprinkler system.


Friday, December 30, 2016

Response: We have revised sheets TBL& A1 to show the building having an automated sprinkler system. Please review for approval.

12/30/2016 sboike

Is there equipment that meets NFPA 1.30.2.8.1?  


Friday, December 30, 2016

Response: There is no equipment needed for repair work other than basic hand tools. The process is to pull truck in and repair crane on the truck. There is a bridge crane in the space. Please consider for approval.

12/30/2016 sboike

NFPA 1.30.2.9 Are there going to be return air openings?


Friday, December 30, 2016

Response: yes, for office area and fresh air intake and exhaust fan provided in service areas. Please refer to sheet M1 for approval.

12/30/2016 sboike

NFPA 1.30.3.3.1 Are there going to be waste handling tanks?


Friday, December 30, 2016

No waste handling tanks and no oil change associated with this project. Please consider for approval.

12/30/2016 sboike

Please address the DRC requirement for the private hydrant.


Friday, December 30, 2016

Response: Civil engineer will address this comment in their resubmittal. Please consider for approval.

12/30/2016 sboike
An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.  
An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FAC 61G15-32.002(5) We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.