Plan reviewed for 14 heads added or relocated. Reviewed using FFPC 6th edition effective Dec. 31, 2017. Reviewer: Sandra Boike 904 209 1741 Victoria Vitori 904 209 1748 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
4/16/2018
| sboike |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package.
To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best). Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review. Items labled "informational only" are for the contractor.
|
4/4/2018
| sboike |
|
|
1) Head count in the sprinkler legend is different than the plan. Please address.
Monday, April 16, 2018
Head count has been updated.
|
4/16/2018
| sboike |
|
|
2) How are you accommodating the mezzanine?
Monday, April 16, 2018
Called Jon on the application to clarify the mezzanine. He stated he did not know there was a enclosed mezzanine above the seating. Please resubmit addressing the mezzanine.
|
4/23/2018
| VVitori |