| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for 190 occ load assembly. approx. 3291 sqft. Reviewed using FFPC 5th edition. Reviewer: Sandra Boike 904 209 1741 Victoria Vitori 904 209 1748 To schedule fire inspections please call 209-1740x1 then 1 again. To leave a message extension 1 then 2. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
1/3/2018
| sboike |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package.
To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best). Please use the Florida Fire Prevention Code 5th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review. Items labled "informational only" are for the contractor.
|
1/3/2018
| sboike |
|
|
What locking mechanism is on the exterior gate under the covered patio? Shall be in compliance with NFPA 101:7.2.5.
Wednesday, January 03, 2018
Architect Response: Original patio gate, no new gate will be added.
Reviewer notes: Please remember if occupancy load exceeds 100 than panic hardware required.
|
1/3/2018
| sboike |
|
|
Page A4.1 panic hardware required on all doors where occupant load exceeds 100. How are you meeting NFPA 101.12.2.2.2.3. Please remember no other locks can be used on the same door as panic hardware. NFPA 101.7.2.1.5.12.
Wednesday, January 03, 2018
Architect Response: Door schedule updated.
|
1/3/2018
| sboike |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- fire sprinkler system - kitchen hood - kitchen suppression system
|
1/3/2018
| sboike |
|
|
How are you meeting NFPA 101:7.4.1.1.? Two means of egress required for every story.
Wednesday, January 03, 2018
Architect Response: Per NFPA 101:12.2.4.5 occ load for mezzanine is less than 50. NFPA 101:12.2.5.1.2 common path of travel being met.
|
1/3/2018
| sboike |