SJC Home
Clearance Sheet C2016-000720

 Department IssuesSigned OffIntl

1) Please provide energy sheets for heated and cooled area.

 

2) Sheet 6 shows fixture table in 2014 code needs to reflect 2017 FBC plumbing.

 

3) Per 2017 FBC Plumbing section 411 S-2 occupancy requires emergency shower and eyewash station .

 

4) Sheet 7 Electrical page needs to indicate occupant sensor controls per C405.2.1 of the FBC Energy Conservation code