Clearance Sheet C2014-002850

 Department IssuesSigned OffIntl

1. Missing Disclosure Statement

According to Florida Statutes 481.2131, Interior design documents prepared by a registered interior designer shall contain a statement that the document is not an architectural or engineering study, drawing, specification, or design and is not to be used for construction of any load-bearing columns, load-bearing framing or walls of structures, or issuance of any building permit, except as otherwise provided by law. Please provide this statement on the sumbitted plans.

 

2.  Mechanical, Electrical, Plumbing Drawings

FBC-Building section 107.1 requires submitted drawings to be completed by a registered designed professional.  Florida Statutes, 471.003 (h) reads - Any electrical, plumbing, air-conditioning, or mechanical contractor whose practice includes the design and fabrication of electrical, plumbing, air-conditioning, or mechanical systems, respectively, which she or he installs by virtue of a license issued under chapter 489, under part I of chapter 553, or under any special act or ordinance when working on any construction project which:

1. Requires an electrical or plumbing or air-conditioning and refrigeration system with a value of $125,000 or less; and
2.a. Requires an aggregate service capacity of 600 amperes (240 volts) or less on a residential electrical system or 800 amperes (240 volts) or less on a commercial or industrial electrical system;
b. Requires a plumbing system with fewer than 250 fixture units; or
c. Requires a heating, ventilation, and air-conditioning system not to exceed a 15-ton-per-system capacity, or if the project is designed to accommodate 100 or fewer persons.
Please indicate on the plans, the license holder's name and license number.
 
General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.