SJC Home
Clearance Sheet C2014-001860*006

 Department IssuesSigned OffIntl

Plan reviewed for kitchen fire suppression system. This system is pre-engineered and manufactured by  by Captive Aire. The kitchen fire suppression system is protecting 2 10'3" hoods. Each hood  has 2 tanks that are prefilled and manifolded and capable of supplying 40 points.

Hood 1- Tanks use 32 of 40 points

1 duct nozzle, 2 plenum nozzles, 3 covering appliance and 2 nozzles covering an upright broiler.

Hood 2- Tanks use 39 of 40 points

1 duct nozzle, 2 plenum nozzles, 2 nozzles for the overhead salamander and 5 nozzles for appliance coverage.

Hood 1 and 2 have fire stat thermal detector located at the entrance of the duct.

2" gas shut off is electric and requires manual reset

Electric Remote push system activation

Class K wet chemical fire extinguisher provided

Shunt trip for gas and electric and make up air

This occupancy does have a fire alarm. Plans show connection available on panel.  

Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: J.L. Hatcher 904-209-1741, jlhatcher@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

NFPA 96: 4.6.1 requires plans to show number, type, size and position of all appliances served.

Provide plan detail showing appliances. Provide spec sheets for appliances being used.

 

Hood #1

It appears the upright broiler will be on a wheeled cart.

Provide detail of how this will be arranged or attached to the wall.

How will the hard piped suppression nozzles remain in place to assure they are positioned correctly if these is moved ?

 

Hood 2

Provide detail how the nozzles for the salamander will be piped and or protected. Routinely the salamanders are attached to the wall and therefore do not create issues when stationary and hard piped.

 

Hood 2 (OL-4 and OL-5 nozzles).

Please provide information from captive aire regarding how these nozzles differ.

 

INFORMATIONAL ONLY

Gas cooking appliances on casters shall have a restraint to prevent damage of gas line. NFPA 54.9.6.1.1

Movable cooking equipment shall be provided with a means to ensure that it is correctly positioned in relation to the appliance discharge nozzle during cooking operations. NFPA 17a 5.6.4

All equipment manuals shall be provided to the owner. NFPA 17A.4.4.2.3

Multiple hoods shall be labeled with corresponding manual activations devices. NFPA 17a 4.4.2.5