Clearance Sheet C2014-001860*006

 Department IssuesSigned OffIntl

Plan reviewed for kitchen exhaust hoods for 3,328 sf restaurant.

Roof appears to be flat.

Hood 1- 10' long 60" wide and 30" high.

Hood 2- 10' long 60' wide and 30" high

Hood 1  Fan  Captive Aire DU85

Hood 2 Fan  Captive Aire DU85

Roof plan -At least 10'seperation maintained from KEF and MUA.

Make up Air (MUA-1) Captive Aire

16" duct  gauge Stainless steel sealed with 3M fire barrier 2000 Plus to seal duct joints and duct insulation for zero clearance to combustibles 

Built in 3" air separation offset from hood to wall.

Wall from floor to top of hood-durock cement board with stainless and  4" minimum offset (piping)

2" electric gas valve

Digital controller to activate exhaust fans based on temperature differences between ambient air and duct temperature sensor.

Digital controller to disable MUA supply fan and activate exhaust fans, activate the shunt trip for all electric including plus and gas valve when fire conditions are detected



Reviewed using FFPC 8th edition effective Dec. 31, 2023. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: J.L. Hatcher 904-209-1741, jlhatcher@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

7/24/2025 jlhatcher

INFORMATIONAL ONLY

Gas cooking appliances on casters shall have a restraint to prevent damage of gas line. NFPA 54.9.6.1.1

Movable cooking equipment shall be provided with a means to ensure that it is correctly positioned in relation to the appliance discharge nozzle during cooking operations. NFPA 17a 5.6.4

All equipment manuals shall be provided to the owner. NFPA 17A.4.4.2.3

Multiple hoods shall be labeled with corresponding manual activations devices. NFPA 17a 4.4.2.5

Assure fan base seal is installed for final

Fans-Electric whip shall have a minimum of 3' conduit/wire. Tilt test

Be prepared to leak test using Fog machine- No smoke bombs allowed.

 

7/24/2025 jlhatcher