| Department Issues | Signed Off | Intl |
|
Plans for a 35 device addressable fire alarm system with voice evacuation (pre recorded voice) utilizing a GEi064 panel. This will be installed in a new restaurant located in an existing building.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code. For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.
|
7/16/2025
| RDowling |
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the permit center. You may not make handwritten alterations on signed and sealed plan pages. B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size. C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8". - Code responses shall reference Florida Fire Prevention Code, 8th Ed.
|
7/16/2025
| RDowling |
|
1) A pull station is required at gate 103 (west of bar) per the life safety plan sheet A1.0.
|
7/16/2025
| RDowling |
|
2) Based on the latest revision approved by our office on 6/23/25, the double gates indicated on the shop drawings do not exist Gate 103A which is the single gate shown near the double gates is the current exit. Relocate the pull station accordingly.
|
7/16/2025
| RDowling |
|
3) It does not appear that the area of the cook line through the rear kitchen exit has adequate visual coverage. Please verify.
|
7/16/2025
| RDowling |
|
4) What is the dry chemical suppression system referenced in the fire riser room?
|
7/16/2025
| RDowling |
|
5) What are the purposes of the monitor modules indicated near the cook line? (x4)
|
7/16/2025
| RDowling |
|
6) I do not see that the kitchen suppression system is monitored. (wet chemical)
|
7/16/2025
| RDowling |
|
7) Double check visual coverage for exterior seating area 103. It appears that visual coverage is missing in both the area west of the bar and the area to the east and southeast of the bar near the stage and seating area near gate 103A.
|
7/16/2025
| RDowling |