Clearance Sheet C2014-000580

 Department IssuesSigned OffIntl

Plan APPROVED for converting a 2 story 4000 sqft residential home to an office building which is not protected with fire sprinkler system. This is reviewed under 2010 Flordia Fire Prevention Code as business. 

There will only be one business in this building.

3/28/2014 smurray

Deadends can not exceed 20 feet in building not protected with fire sprinkler system. (NFPA 101, 38.2.5.2.2) There are 3 shown on the plan. (1 upstairs, 2 downstairs)3/20/14- There is still one deadend over 20 feet downstairs. 3/28/14-corrected.

3/28/2014 smurray

The balconies on the second floor do not meet the criteria of an exit. Please remove the signs. 3/20/14-Comment not addressed.

3/28/2014 smurray
The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required. (NFPA 101, 7.8.1) This will be checked at the final. 3/20/2014 smurray

Provide the width of the stairs in compliance with NFPA 101, 7.2.2.2.1.2. 3/20/14-Stairs meet the minimum clearance of 36".

3/20/2014 smurray

Two exits are required from every story unless exceptions are met.
-Common path of travel less than 100 ft
-Occupant load not to exceed 30 people
-Total travel distance to outside not to exceed 100 ft
-Exit enclosed 1 hour and discharges directly to the outside. (NFPA 101, 7.1.3.2 and 7.2.2.3.1.5) 3/20/14- Although the stairs enclosure is now rated, it now discharges inside the first floor in an unprotected area and does not lead directly to the outside. 3/28/14-corrected.

3/28/2014 smurray

No storage under stairs unless exception met. (NFPA 101, 7.2.2.5.3) 3/20/14-It is noted stair enclosure will be rated 1 hour and no storage under stairs.

3/20/2014 smurray
Air handlers with more than 2000 CFM are required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space.  (NFPA 90A,6.4.2) 3/28/14-CFMs are 2000 so no duct dets required. 3/28/2014 smurray

Any concealed combustible space in which bldg materials having a flame spread index greater than Class A shall be draftstopped including but not limited to unoccupied attic space. This space shall be subdivided by draftstops into areas not to exceed 3000 sqft. NFPA 101, 8.6.10 3/28/14-This is under 3000 sqft.

3/28/2014 smurray
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". (NFPA 1, 10.12.1.2) Will be checked at final. 3/20/2014 smurray
Locks on exit doors or access exit doors shall not require the use of a key, a tool, or special knowlege or effort for operation from the egress side unless they meet the requirements of NFPA 101, 7.2.1.5. Will be checked at final. 3/20/2014 smurray

All new elevators shall conform to the Fire Fighters' Emergency Operations requirements of ASME A17.1/CSA B44, Safety for Elevators and Escalators. (NFPA 1, 11.3) 3/20/14-Comment not addressed. 3/28/14-Corrected.

3/28/2014 smurray

All unit equipment (emergency lighting) shall be wired ahead of switch or control of normal lighting circuit serving that area. The branch circuit feeding the unit equipment shall be the same branch circuit as that serving the normal lighting in the area and connected ahead of any local switches. The branch circuit that feeds unit equipment shall be clearly identified at the distribution panel. In a separate and uninterrupted area supplied by a minimum of three normal lighting circuits, a separate branch circuit for unit equipment shall be from the same panel board as that of the normal lighting circuits and provide a lock-on feature.

3/28/2014 smurray
The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. (NFPA 101 7.2.1.3) 3/28/2014 smurray

If this is light-weight truss-type construction (repetitive wood  or light guage steel framing) placement of approved Firefighting Safety Warning Sign (Maltese Cross) shall be placed on structure in accordance with FS 633.027 and FAC 69A-60.008 (size, color, height placement)
Will be checked at final.

3/28/2014 smurray