| | Department Issues | Signed Off | Intl |
|
|
Windows and doors installed in masonry construction shall be flashed as per Section 703.8. Please indicate on drawings the approved method being used listed in the Code section.
|
3/20/2014
| ccrain |
|
|
Please provide site specific available Fault Current Letter from utility company as per NEC 2008 Section 110.9.
Fault Current Letter 21,110
|
3/20/2014
| ccrain |
|
|
Provide a complete clearance sheet and two DRC approved site plan.
3/20/2014 Unable to locate clearance sheet.
|
4/1/2014
| ccrain |
|
|
Preliminary reviews are one time reviews submitted prior to approval of a clearance sheet and site plan. Because of this, and the documentation and plans are usually insufficient and incomplete, a full review cannot be accomplished without the possibility of adding additional comments at time of future submittals.
|
4/1/2014
| ccrain |
|
|
As per 2012 Florida Accessibility Code for Building Construction (FACBC) where drinking fountains are provided and required by the Florida Plumbing Code, they shall be in accordance with Section 211 of the FACBC. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with 602.1 through 602.6 and one drinking fountain shall comply with 602.7
|
3/20/2014
| ccrain |
|
|
As per Section 206.4.1 of the Florida Accessibility Code for Building Construction (FACBC) 2012 please note that in addition to the entrances required by Section 206.4.2 through 206.4.9, at least 60 percent of all public entrances shall comply with Section 404 of FACBC.
3/20/2014 Building elevations do not show ramps.
|
4/1/2014
| ccrain |
|
|
Electrical plans shall include but not be limited to: scaled floor plans for all floors and/or units. Lighting and power requirements shall meet the minimum standards of the 2008 National Electric Code. Diagrams, schedules and calculations of all electric distribution systems are required in addition to electrical feeder wire sizes, conduit sized, and over-current device sizes. Smoke detectors shall be installed as per the 2010 FBC.
3/20/2014 Show panel locations on the plans. Riser diagram states two 200 amp panels, plans show one 250 amp?
|
4/1/2014
| ccrain |
|
|
Mechanical requirements shall follow the 2010 Florida Building Code Mechanical also the information listed in the FBC 2010 Section 107.3.5 and shall include but not be limited to: Floor plans for all floors and units, show all equipment, refrigerant and condensate drain line locations, make-up air calculations, duct systems, ventilation & exhaust systems and include the method of providing penetration protection of walls, floors and ceilings including indication of fire dampers.
3/20/2014 Unable to locate mechanical drawings.
4/1/2014 A hold will be placed for mechanical drawings.
|
4/1/2014
| ccrain |
|
|
Plumbing requirements shall follow the 2010 Florida Plumbing Code. Also submit the information listed in the FBC 2010 Section 107.3.5 which shall include but not be limited to: Floor plans for all floors and units, showing all fixture requirements, water supply piping, sanitary drainage, water heaters, vents, roof drainage, back-flow prevention, plumbing risers, grease traps, environmental requirements and location of water supply line. Plans shall include all sizing and locations and method of providing penetration protection.
|
3/20/2014
| ccrain |
|
|
1. As required by the Board of Engineers a letter or other document must be submitted indicating the Engineer of Record has reviewed the truss submital package. This document must be signed/sealed and submitted along with the truss/structure engineering, please submit.
|
3/20/2014
| ccrain |
|
|
Two exits are required from second floor.
|
3/20/2014
| ccrain |
|
|
Shaft required for stairway penetrating floor system.
Shaft enclosure must be from floor to upper most ceiling and details of rated ceiling needed.
|
4/1/2014
| ccrain |
|
|
Please provide connector details for new framed balcony.
|
3/20/2014
| ccrain |
|
|
Please remove all notes that refer to residential stairway construction.
3/20/2014 Plans state max of 7.50 inches for stair riser. Please correct.
|
4/1/2014
| ccrain |
|
|
Provide detail for ADA compliant shower.
|
3/20/2014
| ccrain |
|
|
It appears that the water heater will void the electrical panel clearances.
|
3/20/2014
| ccrain |