| | Department Issues | Signed Off | Intl |
|
|
Plan APPROVED for a 9026 sqft discount store not protected by fire sprinkler or fire alarm system. This is reviewed under 2010 Fl Fire Prevention Code as mercantile.
|
12/12/2012
| smurray |
|
|
Please show a clear path through the receiving area so that employees can not get trapped in this room.
|
12/12/2012
| smurray |
|
|
It was not clear if the front sliders at the front exit are break away doors or if the force required to open the door in case of loss of power is less than 30 lbf. Please provide documentation. NFPA 101, 7.2.1
|
12/12/2012
| smurray |
|
|
The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required. (NFPA 101, 7.8.1)
|
12/12/2012
| smurray |
|
|
Exit signs are required to be seen throughout the store. Additional signs may be needed depending on the height of shelving. NFPA 101, 7.10
|
12/12/2012
| smurray |
|
|
FS 633.061 requires a license or permit of organizations & individuals who: service, recharge, test, mark, inspect, install or hydrotest fire extinguishers. It will be necessary to use a Licensed Fire Extinguisher Contractor for identifying the location & type of extinguisher to use.
|
12/12/2012
| smurray |
|
|
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". (NFPA 1, 10.12.1.2)
|
12/12/2012
| smurray |
|
|
The elevation of the floor surface on both sides of a door shall not vary by more than a
1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. (NFPA 101 7.2.1.3)
|
12/12/2012
| smurray |