Plan REJECTED for 100 sqft fire pump house. This is reviewed under 2010 Fl Fire Prevention Code and NFPA 20.
A fire pump bldg must be either: *Protected with fire sprinkler system and rate pump house 1 hour or separated 50 feet from the bldg it is protecting *Separated from the bldg is it protecting by 50 feet or rate pump house 2 hours. (NFPA 20, 5.12.1.1) Please provide documentation that a 100 sqft bldg is large enough to be able to make any necessary repairs on the fire pump.
|
| |
|
|
Please provide documentation on an approved heat source for maintaining the minimum temperature of 40 degree Fahrenheit. NFPA 20, 5.12.2.1
|
| |
|
|
Provide documentation on how artificial light is being provided in pump house. NFPA 20, 5.12.3
|
| |
|
|
Provide documentation on how emergency light is being provided. NFPA 20, 5.12.4 A flashlight is acceptable.
|
| |
|
|
Provide documentation of ventilation of the pump house. NFPA 20, 5.12.5
|
| |
|
|
Floors shall be pitched for adequate drainage of escaping water away from critical equipment and be provided with a drain that will discharged from a frost free location. NFPA 20, 5.12.6
|
| |