Please provide site specific available Fault Current Letter from utility company as per NEC 2008 Section 110.9.
|
| |
|
|
Please revisit the occupancy classification of this project and apply all applicable requirements to the new occupancy classification.
|
| |
|
|
Please provide the manual N and manual D to complete the energy package.
|
| |
|
|
An electrical service disconnect must be provide at the exterior of the building or the service meter can and panel must be back to back.
|
| |
|
|
Please provide the metal building sealed shop drawings that are to be review by engineer of record.
|
| |
|
|
Need current product approval number for store front.
|
| |
|
|
Please state the R-value of the roof area that is to be the building envelope.
|
| |