Please provide site specific available Fault Current Letter from utility company as per NEC 2008 Section 110.9.  

Please revisit the occupancy classification of this project and apply all applicable requirements to the new occupancy classification.

 

Please provide the manual N and manual D to complete the energy package.

 

An electrical service disconnect must be provide at the exterior of the building or the service meter can and panel must be back to back. 

 

Please provide the metal building sealed shop drawings that are to be review by engineer of record.

 

Need current product approval number for store front.

 

Please state the R-value of the roof area that is to be the building envelope.