SJC Home
Clearance Sheet C2012-000885*001

 Department IssuesSigned OffIntl

1. Code Reference
The plans are referencing the 2009 building code.  The current building code is the Florida Building Code 2010 edition.  Please change the code reference to the correct year.  The wind speed is indicated as 120 mph basic wind speed.  Section 1609, figure 1609C for Risk Category 1 buildings shall be used to determine the ulimate wind speed for this structure.  Please update the basic wind speed to the current ultimate wind speed.

 
Informational General Notes: Your re-submittal shall include two complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be marked as "old set" and shall be included in the re-submittal.
If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again.
ALL ITEMS changed or revised on plans and documents shall be identified by circling, clouding or identified by some other legible method. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW.