| | Department Issues | Signed Off | Intl |
|
|
Plan REJECTED for fire alarm system inside work release bldg.
A FULL REVIEW HAS NOT BEEN COMPLETED. PLEASE ADDRESS:
The engineer of record for this fire protection system, who set forth the sprinkler/fire alarm design criteria is Steve Kowabany. The shop drawings were submitted with a seal from Robert Worth. Per FAC 61G15-32.002(5)(6) after the Fire protection system engineering documents (Criteria) is submitted with the building plans, the shop drawings, when submitted, require no additional engineering input or seal. Please either: 1) Resubmit sprinkler/fire alarm shop drawings that are not signed and sealed. or 2) Have Robert Worth submit a registered letter to Steve Kowabany seeking to reuse his already sealed contract documents therefore assuming all legal responsibility for the system in accordance with FAC 61G15-27.001. or 3) Have the owner or project engineer submit a letter to our office completely removing Steve Kowabany as engineer of record for the project. or 4) Have the engineer of record provide a note on the shop plans they approve for design requirements.
|
| |