| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for fire suppression system. Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: Anthony Gedris 904-209-1741 Aaron Connell
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
2/3/2022
| aConnell |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications must be submitted to the Permit Center as a resubmission for the original project.
Effective 1/01/2022 you must include a written response to comments summary to clarify and illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
Resubmittals will not be approved without a response to comments.
|
2/3/2022
| aConnell |
|
|
1)-No manual was submitted for the Ansul R-102 suppression system.
|
2/3/2022
| aConnell |
|
|
2)- Suppression system in the plan does not support the large flat grills as submitted; I cannot find in the Ansul R-102 manual any documentation and/or figure that supports or resembles the plan submitted. If there is, please submit any documentation or correspondence from Ansul that accepts this suppression model.
2/3/2022- After further correspondence from Ansul Representative, this suppression model is acceptable. A Connell
|
2/3/2022
| aConnell |