Clearance Sheet C2011-000101*014

 Department IssuesSigned OffIntl

Plans for a 5199sf interior buildout of an existing space, located in a building that is equipped with fire sprinklers.  The space was designed and reviewed as Mercantile.


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1) INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:

- Sprinkler
- Hood
- Kitchen Suppression
- CO2 alarm

 

2) As submitted,  the common path of travel as measured from the walk in freezer is ~94 feet.  The maximum permitted is 75'.  NFPA 101:12.2.5.1.1. 

 

3) The wall between the proposed space and the pet supermarket must either be a 2 hour wall, or the building sprinkler system must be electronically supervised by a fire alarm system, which includes all sprinkler valves including the backflow preventer.  NFPA 101: table 6.1.14.4.1(a), and 9.7.2.

 

4) Ensure that the reclaimed wood indicated meets the interior finish requirements of the code and as indicated on sheet G-1. Provide specs for the product or specs for the product that will be applied to meet this. 

 

5) Provide specification sheets for the used oil tank referenced on sheet A-2.

 

6) A CO2 alarm is indicated on sheet A-2 to be submitted separately by contractor.  A hold has been placed at insulation (109) for this. 

 
Informational

7) Info Only

Ensure that the cooler and freezer doors do not require a key, tool, or special knowledge to open from the egress side.  This will be verified during final. 

 
Informational

8) Info only

The front doors are marked as existing on the door schedule.   Ensure that one of the two options are met which will be verified at the time of final. 

-Panic hardware is installed on both doors that releases all locks and latches

- Keyed locking devices are installed on doors.  No latches on doors permitted with this option.  Also ensure that the requirements of 101:7.2.1.5.5 are met. NFPA 101:12.2.2.2.3, 12.2.2.2.4.   

 

9) Overall the emergency lighting looks good using the wall mounted and ceiling mounted devices.  Provide specifications, so I can verify coverage.  Ensure you adhere to the spacing, mounting height, and coverage requirements.