Clearance Sheet C2010-000771

 Department IssuesSigned OffIntl

Plan APPROVED for Ansul R-102 3 + 1.5 gallon kitchen fire suppression system installed under 8'9" hood. 12 out of 16 points used. Kitchen equipment from L to R: 4 eye range, 36"x24" charbroiler, 2 fryers.

There shall be at least 16" space btwn fryer and surface flames from adjacent cooking equipt unless a minimum 8" high steel or tempered glass baffle plate is installed btwn fryer and surface flames. (NFPA 96)

At the time of this review, the kitchen exhaust hood plan has not been submitted. Please pass on to contractor, do NOT hang kitchen duct without a light test from the Fire Marshal's office.

11/8/2010 smurray