2. Please provide a HVAC duct layout, including supply, return, exhaust, and makeup air. Include an equipment schedule showing Total cooling (MBH), Sensible (MBH), Minimum SEER, Heating (MBH), Minimum HSPF, Supply Air (CFM), Outside Air (CFM), Static Pressure (in. wc), Motor (HP), Voltage, and Auxiliary Heat (KW). Note: Outside air is required to comply with ASHRAE 62.1. Note: In addition a commercial kitchen hood complying to FBC-M section 506&507 is required with adequate makeup air.