SJC Home
Clearance Sheet C2010-000771

 Department IssuesSigned OffIntl

Plan APPROVED for change of use from 1380 sqft office to restaurant. This is reviewed under 2007 Fl Fire Prevention Code as mercantile. Occupant load 46.

6/29/2010 smurray
The Grease Exhaust Hood noted on this page and several other pages throughout these plans are conceptual. A separate permit will be required by the Fire Marshal. A HOLD will be placed on the building permit and NO INSPECTION past slab will be done until this permit is submitted & approved. 6/29/2010 smurray
The Grease Exhaust Hood requires a FIRE SUPPRESSION SYSTEM. The Fire Marshal's Office requires a separate FIRE SUPPRESSION PERMIT and a HOLD will be placed on the building permit whereby NO INSPECTIONS past slab can be done until this permit is approved. 6/29/2010 smurray
FS 633.061 requires a license or permit of organizations & individuals who: service, recharge, test, mark, inspect, install or hydrotest fire extinguishers. It will be necessary to use a Licensed Fire Extinguisher Contractor for identifying the location & type of extinguisher to use. 6/29/2010 smurray

If this is light-frame truss-type construction (repetitive wood  members)placement of approved Firefighting Safety Warning Sign (Maltese Cross) shall be placed on structure in accordance with FS 633.027 and FAC 69A-60.008 (size, color, height placement)

6/29/2010 smurray