Plan reviewed for installation of 30 fire alarm devices in newly renovated educational space in suites 24, 25, 26, and 27. Occupancy is new education.
Reviewed using FFPC 6th edition effective Dec. 31, 2017. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Plans are APPROVED.
Reviewer: D. Feagle 904-209-1721
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
************************
Wednesday, December 16, 2020 DF: Held 1st submittal at customer request for new sheets to be printed. Received the adjusted sheets.
|
12/16/2020
| dfeagle |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
12/16/2020
| dfeagle |
|
|
1) Corridor 119 missing audio/visual device. 101:14.3.4.3.1.1
Provide a audio / visual device in the corridor.
Wednesday, December 16, 2020 DF: Device now shown.
|
12/16/2020
| dfeagle |
|
|
2) Show / Note on the plans the location of the FACP / Voice Evac panels.
Wednesday, December 16, 2020 DF: Now shown.
|
12/16/2020
| dfeagle |
|
|
3) Fire Alarm Matrix does not identify the waterflow actuating the common alarm signal indicator and actuating the audible alarm signal. 101:14.3.4.2.2
Adjust the Fire Alarm Matrix to reflect the waterflow activity.
Wednesday, December 16, 2020 DF: Response: This isn't part of our retrofit sprinklers in this area. Any new sprinkler heads are part of the malls fire sprinkler system. I contacted Chris with Village Key regarding the FA water flow tie in to the FACP. Per Chris the FACP will call the monitoring company if water flow is activated.
|
12/16/2020
| dfeagle |
|
|
4) Missing the manufacturers spec sheets for: ceiling mounted speaker strobes, ceiling mounted strobes, wall mounted strobes,
Provide missing spec sheets.
|
12/16/2020
| dfeagle |
|
|
5) Missing notification device in bathroom / janitor room 103/104.
Provide notification device in this area.
Wednesday, December 16, 2020 DF: Response: Stalls are half stalls they do not go all the way up in the restroom.
|
12/16/2020
| dfeagle |