SJC Home
Clearance Sheet C2009-001465

 Department IssuesSigned OffIntl

1. Submit a DRC approved site plan showing an accessible route connecting the building to the sidewalk at the street, and accessible parking spaces which are of the correct size. Friday, November 20, 2009 This is an existing building that was permitted before Oct. 1,1997 via phone conversation with Mr. Lucas, therefore as an alteration the FACBC does not apply.
The square footage issue still needs resolve.
As per the Florida Accessibility Code for Building Construction (FACBC) Section 11-4.1.2 states - An accessible site shall meet the following minimum requirements: (1) At least one accessible route complying with Section 11-4.3 shall be provided within the boundary of the site from public transportation stops, accessible parking spaces, passenger loading zones (if provided) and public streets or sidewalks, to an accessible building entrance (2)At least one accessible route shall connect accessible buildings, accessible facilities, accessible elements and accessible spaces that are on the same site (3) All objects that protrude for the surfaces or posts into circulation paths shall comply with Section 11-4.4. (4) Ground surfaces along accessible routes and in accessible spaces shall comply with Section 11-4.5 and (5) accessible parking spaces.
On the Site plan for Construction drawings, please indicate the Gross Floor Area as defined by the Florida Building Code - The floor area within the inside perimeter of the exterior walls of the building under consideration, exclusive of vent shafts and courts, without deduction for corridors, stairways, closets, the thickness of interior walls, columns or other features.    
Please make sure the Gross Floor area is indicated on the DRC site plan, and that is the same square footage number depicted on the architectural plans submitted for Building permit; otherwise the issuance of Building permit will not be accomplished until both these numbers correlate, and if not this may require a possible resubmittal to DRC
Please also dimension distance between all buildings and the number of stories.
Please explain the discrepancy between the square footage shown on the application, the plans and the energy calcs, (all should correlate.)

12/2/2009 jdrummond

2. Please mark plans to clarify that a Hi-Lo water fountain will be installed. As per Section 11-4.1 of the Florida Accessibility Code for Building Construction (FACBC), an accessible (hi-lo) drinking fountain is required to comply with Section 11-4.15.1 thru 11-4.15.5 of the FACBC.

12/2/2009 jdrummond

3. Please clarify that the counter at the check-in meets the requirements of accessibility as per the Florida Building Code.  

12/2/2009 jdrummond

4.  Please clarify that the door hardware meets the requirements of Florida Accessibility Code for Building Construction Section 11-4.27 Controls and operating mechanisms - Controls and operation mechanisms required to be accessible by Section 11-4.1 shall comply with Section 11-4.27.  
In addition, please clarify what type of doors are being used as elevations show a, b, and c and schedule showns numbers.

12/2/2009 jdrummond
5. Please clarify that the material on Detail 9 on Sheet A3.1D is not fastened through the stucco but applied and therefore doesn't violate the sealing of the stucco. Please refer to details on plans for flashing wall openings per BOAF First Coast Chapter Codes and Standards Committee Bulletin. www.firstcoastchapter.org "CODES/STANDARDS flashing bulletin 10 04" 12/2/2009 jdrummond
Informational

6.   A hold is placed on the electrical permit until drawingsare submitted and approved to resolve this issue, as discussed via phone with Bryan Shaffer. Wednesday, December 02, 2009 Show the main disconnect on the exterior of the building as the power diagram shows unfused wires to he panel which is not allowed.
Please modify the emergency exits lights to correlate with the path of egress, (the door swing on porch doesn't correlate with rest of plans.)
where are the service outlets for the HVAC equipement outdoors?
Please identify all gfci outlets including those required at the Kitchen area as per NEC 2008.

Electrical plans shall include but not be limited to: scaled floor plans for all floors and/or units.  Lighting and power requirements shall meet the minimum standards of the 2008 National Electric Code.  Diagrams, schedules and calculations of all electric distribution systems are required in addition to electrical feeder wire sizes, conduit sized, and over-current device sizes. Smoke detectors shall be installed as per the 2007 FBC section 907.2.6.2.3. 
Electrial reviewed by: Joe DaCosta