| | Department Issues | Signed Off | Intl |
|
|
#1
sheet t1.0 lists bldg. type3b / 2nd sheet t1.0 lists type 2b ?
|
8/18/2015
| fbecza |
|
|
#2
separate unit build-outs require separate permits / units 204 & 205 now one unit , 208 & 209 separate units
|
8/18/2015
| fbecza |
|
|
#3
per fbc 507.1 doors in unit 204 / 205 cannot reduce the width of egress by more than half
|
8/18/2015
| fbecza |
|
|
#4
show both panels for units 208 & 209 on power riser diagram
|
8/18/2015
| fbecza |
|
|
#5
panels 'a' and 'pp1' circuit layouts not similar 2 ahu's and 2 water heaters on same panel in separate units 208 & 209
|
8/18/2015
| fbecza |
|
|
#6
need summary of work to be done in units 204 & 205 with code summary of combined units
|
8/18/2015
| fbecza |
|
|
#7
provide written response to all review comments
|
8/18/2015
| fbecza |
|
|
#1 resubmit
units 208 and 209 are two separate units and two separate businesses therefore require two separate permits / units 204 and 205
show a common door in the separation partition that makes it one business and one unit
|
8/31/2015
| fbecza |
|
|
#2
same comment as previous review units 208 and 209 are separate units and require separate permits for different businesses
and two certificates of occupancy
|
8/31/2015
| fbecza |