SJC Home
Clearance Sheet C2009-000356*007

 Department IssuesSigned OffIntl

Plan APPROVED for interior build out for suites 208 and 209 which includes adding 1 hour wall to separate the suites, 900 sqft each, not protected with fire sprinkler system for medical offices. This is reviewed under FFPC 5th edition as business.

8/18/2015 SMurray
Locks on exit doors or access exit doors shall not require the use of a key, a tool, or special knowledge or effort for operation from the egress side unless they meet the requirements of NFPA 101, 7.2.1.5. 8/18/2015 SMurray
FS 633.061 requires a license or permit of organizations & individuals who: service, recharge, test, mark, inspect, install or hydrotest fire extinguishers. It will be necessary to use a Licensed Fire Extinguisher Contractor for identifying the location & type of extinguisher to use. 8/18/2015 SMurray