Plan reviewed for "renovation" of existing building. Submitted plans indicate 2390sf while original building plans indicate 2632sf. Reviewed using FFPC 5th edition.
Reviewer: Sandra Boike 904 209 1741 
Victoria Vitori 904 209 1748
To schedule fire inspections please call 209-1740x1 then 1 again. To leave a message extension 1 then 2.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

1) Unable to provide full review as no code analysis has been provided nor enough information to show compliance with Code. The following are examples of missing items but not all. Please reference the appropriate chapter(s) of Florida Fire Prevention Code for requirements that will be checked.

Occupancy type(appears to be storage but needs to also include what classification of hazard of contents) 101:42.1.5? Identify commodity class of storage 1:34.

What Code(s) used?

Occupant Load?

Exit location(s)? Signage?

Emergency lighting?

Height of storage? Rack, stack...? Furniture/shelving layout showing aisle?

Will idle pallets be stored inside or outside? Where? How many? How? Type (plastic, wood)?

 

QUESTIONS THAT MAY TRIGGER SPECIAL CONSIDERATION FOR STORAGE OCCUPANCIES Please write YES or NO on each line if this building is going to be classified as stroage. This info must accompany the plans. NFPA 1:20.15 and 1:34  
_____Will you allow STORAGE OF HIGH-PILED COMBUSTIBLES over 12 feet high in areas greater than 2500 sq ft?
_____Will you allow GROUP A PLASTICS STORAGE in excess of 5 ft in height over an area exceeding 2500 sq ft in area?
_____Will you allow RUBBER TIRE STORAGE?
_____Will you allow RECORD STORAGE?
_____Will you allow CELLULOSE NITRATE MOTION PICTURE FILM STORAGE?
_____Will you allow AEROSOL PRODUCTS STORAGE?
_____Will you allow FLAMMABLE&COMBUSTIBLE LIQUID STORAGE?
_____Will you allow PORTABLE LP-GAS CONTAINERS storage inside the bldg?
_____Will you allow OXIDIZER STORAGE?
_____Will you allow ORGANIC PEROXIDE