Plan APPROVED for remodel of 4235 sqft suite inside a covered mall. This is reviewed under 2007 Fl Fire Prevention Code as mercantile.
|
2/25/2010
| smurray |
|
|
Maintain 36 inch aisles throughout the store and to the exits. NFPA 101, 36.2.5.6.
Maintain 44 inch aisle throughout the storeroom to the exit. NFPA 101, 36.2.5.11.
|
2/25/2010
| smurray |
|
|
The scope of work for this project is in the area of an existing fire sprinkler system. A separate fire sprinkler permit is required for any modification to this system. A hold is placed on the Building Permit and no inspections will be done until this Fire Sprinkler Permit is submitted & approved. (NFPA 1,13.1.1.1)
|
2/25/2010
| smurray |