Clearance Sheet C2008-000049

 Department IssuesSigned OffIntl

Plan resubmittal to address the previus comments.  The previous comments have been addressed.  Thy system is designed as a NFPA 13 wet system with a split riser.  One riser covers 51,155 square feet as the lower system. The second also covers 51,155 square feet as the upper system.  The hazard is light with a density of .10.  There are a couple ordinary hazard areas as indicated on the plans.  Note: This plan is for the aboveground only, a seperate permit will be required for the underground.  

Plans APPROVED

10/3/2008 PJW