SJC Home
Clearance Sheet C2008-000049

 Department IssuesSigned OffIntl

Plan is APPROVED for 58,619 toal sq ft (51,977 sq ft 1st floor, 6642 sq ft second floor) 16 plex movie theatre with 2 retail shells. (These have separate permits.) This was reviewed under 2004 Fl Fire Prevention Code as assembly.

Note: Bldg Dept requires a separate permit for the Type II hood over the popcorn.

4/14/2008 SLM
The Fire Sprinkler Design Criteria is OK for the building permit, Noted a separate permit will be required for the fire protection systems. A HOLD has been placed on the Building Permit and NO inspection can be done past the slab until this permit is approved.
Criteria found on page P-1 for both theatre and retail wings. Riser room for theatre is room 146, located between auditorium 6 & 7 SE backside of bldg. Per FSS 633.539(3) the underground fire main must terminate 1 ft above the finish floor.
4/14/2008 SLM
The UNDERGROUND CONTRACTOR for the installation & hydro test of the fire sprinkler line will require a separate permit. A HOLD will be placed on the building permit and NO inspection past the slab will be done until this permit is submitted & approved. 4/14/2008 SLM
The Fire Alarm Design Criteria is OK for the building permit, Noted a separate permit will be required for the fire alarm systems. A 102 HOLD has been placed on the Building Permit and no inspection can be done past the slab until these permits are approved.
Criteria found on pages E 3.1, 3.2, 4.1 and 4.2. The FACP is located upstairs (pg E4.1, note 5). Remote annunciator is located in lobby (pg E3.1, note 7). A voice evacuation system is required. (NFPA 101, 12.3.4.3.4)
4/14/2008 SLM
The occupant load shall be posted in a conspicuous place near the main entrance/exit from the room. Please refer to the Fire Marshal Notation on the plans as to the approved maximum occupant load to be posted. The Posting should read,"Maximum Occupant Load ______ Persons, by order of the Fire Marshal" (NFPA 101, 12.7.8.3.1)
Auditorium loads: #1:195; #2:126; #3:98; #4:72; #5:72, #6:117, #7:239; #8:298; #9:298; #10:239; #11:117; #12:72; #13:72; #14:98; #15:126: #16:195
Lobby:274; Party Rm A:19; Party Rm B:19;
Total occupancy for bldg: 2852 people
4/14/2008 SLM

Documentation was submitted for interior finish. This documentation is required to be on job site.

4/14/2008 SLM
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) Fire extinguishers not requried in auditorium. NFPA 1, 13.6.1 4/14/2008 SLM
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". (NFPA 1, 10.13.1.2) 4/14/2008 SLM
Provide a EMERGENCY ACCESS KEY BOX near the main entrance. This box is required because there is a fire sprinkler riser or fire alarm control panel located inside this building. An authorization form for the Failsafe access box can be obtained at the Fire Marshal's Office.(4455 Avenue "A", Suite 100, St Augustine, Phone 904-209-1740) 4/14/2008 SLM
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required) (NFPA 90A,4.4.2) 4/14/2008 SLM
All doors that have dead bolts shall use thumb type single cylinder. (NFPA 101, 7.2.1.5) Panic hardware is required. NFPA 101, 12.2.2.2.3. 4/14/2008 SLM
The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required. (NFPA 101, 7.8.1) 4/14/2008 SLM
The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. (NFPA 101 7.2.1.3) 4/14/2008 SLM
Be advised if any construction or installation work which includes but not limited to private underground mains, fire sprinklers, fire alarms is done without pulling the proper permit from the Fire Marshal's office, a STOP WORK written order shall be issued to the responsible party and no work shall continued until this violation is corrected. (NFPA 1, 1.7.11.3) 4/14/2008 SLM