These plans are for a resubmittal of the previously rejected plan. The previous comments have been addressed, the plans are APPROVED. **Please pay special attention to the comment below**.
|
1/16/2008
| PJW |
|
|
At this time I am going to require that you perform the enclosure pressurization/depressurization test be performed and witnessed by our office in accordance with NFPA 2001:3-3.3 and Appendix C. Please contact our office at 209-1744 to schedule this. A hold has been placed on the building permit and no final suppression inspection or fire alarm final inspection will be performed prior to this test.
I was unable to obtain an answer from the Fire Marshal regarding this.
|
1/16/2008
| PJW |
|
|
Note to inspector: Ensure that the computer room still has fire sprinkler head protection from the building fire sprinkler system.
|
1/16/2008
| PJW |