These plans are for a resubmittal of the previously rejected plan.  The previous comments have been addressed, the plans are APPROVED.  **Please pay special attention to the comment below**. 

1/16/2008 PJW

At this time I am going to require that you perform the enclosure pressurization/depressurization test be performed and witnessed by our office in accordance with NFPA 2001:3-3.3 and Appendix C.  Please contact our office at 209-1744 to schedule this.  A hold has been placed on the building permit and no final suppression inspection or fire alarm final inspection will be performed prior to this test.  

I was unable to obtain an answer from the Fire Marshal regarding this.

1/16/2008 PJW

Note to inspector: Ensure that the computer room still has fire sprinkler head protection from the building fire sprinkler system. 