Clearance Sheet C2007-002339*002

 Department IssuesSigned OffIntl

Renovation of the old EOC to the Sheriff Communications Center.

6/30/2010 jpaula

The plans received shows 3 occupancy classifications A, B, and S (FBC302)

1. Please revise the code analyzes show on A-1 to indicate the proposed renovation as mixed use (508.3) accessory occupancy (508.3.2, separated (508.3.3), or nonseparated 508.3.2.  

2. Please revise the occupancy load using FBC Table 1004.1.1.

6/30/2010 jpaula

Sheet M-2 shows an exhaust fan in the Armory exhausting 480 CFM. Please provide makeup air for the exhaust fan, if using existing outside air, please provide the equipment schedule. What is the use of the exhaust fan?.(501.3)

Wednesday, June 30, 2010  Item remain open:  Approving plans with a hold.  Hold framing for Armory Hood make-up air.

6/30/2010 JPAULA

Existing electric panels are shown on E-1,2,4,5,and 6. Please provide a list of the voltage, amps, and phase of the panels shown. (FBC 106.3.5) 

6/30/2010 JPAULA