SJC Home
Clearance Sheet C2007-002339*002

 Department IssuesSigned OffIntl

Plan REJECTED for renovation of existing 10,500 sqft government bldg. This is reviewed under 2007 Fl Fire Prevention Code as mixed occupancy, assembly, business and storage.

Please address the following issues:

 

Regarding the 1932 sqft meeting room, will there be only rows of chairs or will there be tables/desks? Unsecured seating is allowed provided there is not more than 1 seat for each 15 sqft of net floor area and adequate aisles to reach exits are maintained at all times. (NFPA 101, 13.7.9.2) Occupant load is allowed to be increased if all proposed seating diagrams submitted are approved by AHJ. Please submit any other proposed seating configurations.

 

Regarding the new use for an armory, it is unclear if the existing fire sprinkler system is designed to handle the type of hazard and density to contain a fire in this room. Please have your engineer address whether the sprinkler system needs improvements or not based on everything that will be stored in this room. (NFPA 13)

 

It is noted a new fire alarm panel will be installed. Will this alarm panel that currently covers MIS and Supervisor of Elections continue to monitor these areas?

 

Please provide documentation for the flame spread and rating for the acoustical wall coverings. (NFPA 101, 13.3.3)

 

There appear to be card readers in the means of egress. Please confirm whether these are delayed egress doors to exit. (NFPA 101, 13.2.2.2.5)