Plans for a 38 head sprinkler modification to an existing sytsem for an interior buildout.  The plans are APPROVED as submitted.

8/7/2007 PJW
Sprinkler modifications exceeding 20 heads shall be isolated and tested at 200 psi for 2 hours. Modifications that cannot be isolated and sprinkler modifications less than 20 heads, shall be tested at system working pressure. (NFPA 13: 16.2.1.4, 16.2.1.5, and 16.2.1.6) 8/7/2007 PJW