Clearance Sheet C2007-000789*022

 Department IssuesSigned OffIntl

Plan APPROVED for 1026 sqft buildout for a pilates studio inside a multistory bldg protected with fire sprinkler and fire alarm system. This is reviewed under 2010 Fl Fire Prevention Code as business.

8/27/2012 smurray
The scope of work for this project is in the area of an existing fire sprinkler and fire alarm system. A separate fire sprinkler and fire alarm permit is required for any modification to these systems. A hold is placed on the Building Permit and no inspections will be done until this Fire Sprinkler and fire alarm Permit is submitted & approved. (NFPA 1,13.1.1.1) 8/27/2012 smurray
Locks on exit doors or access exit doors shall not require the use of a key, a tool, or special knowlege or effort for operation from the egress side unless they meet the requirements of NFPA 101, 7.2.1.5. 8/27/2012 smurray
FS 633.061 requires a license or permit of organizations & individuals who: service, recharge, test, mark, inspect, install or hydrotest fire extinguishers. It will be necessary to use a Licensed Fire Extinguisher Contractor for identifying the location & type of extinguisher to use. 8/27/2012 smurray