Clearance Sheet C2007-000721*002

 Department IssuesSigned OffIntl

NOTE: A separate permit will be required for the kitchen hood.

8/2/2007 JNP

Provide hotel and restaurant approval.

8/2/2007 JNP

Gas riser   Sheet M-1
Indicate the inlet pressure.
Indicate what type of piping material will be used.

8/2/2007 JNP

Provide a one hour listed penetration for the electrical entering the tenant separation wall.

8/2/2007 JNP

Sheet M-1 shows an existing 4 and 6 ton unit, the energy form shows 2-5 ton.  Please revise the energy form to match.

8/2/2007 JNP