These plans are for a 31 device fire alarm addition to an existing system.  The plans are APPROVED

7/25/2007 PJW
Ensure that the audible signals have a sound level of at least 15 db. above average ambient sound level or 5 db. above the maximum sound level having at least 60 second duration, throughout all occupiable areas. Areas in question will be verified at the time of final. (NFPA 72 7.4.2.1) 7/25/2007 PJW

Note: Received plan in my office 7/24/07....

7/25/2007 PJW