Plan approved for modification of existing sprinkler system in the suite of Pusser's Grille for the first floor only. Any modifications to the second floor requires a separate permit. No CO will be given if a permit has not been pulled for work done on the second floor.

8/22/2007 SLM
Sprinkler modifications exceeding 20 heads shall be isolated and tested at 200 psi for 2 hours. Modifications that cannot be isolated and sprinkler modifications less than 20 heads, shall be tested at system working pressure. (NFPA 13: 16.2.1.4, 16.2.1.5, and 16.2.1.6) 8/22/2007 SLM