SJC Home
Clearance Sheet C2007-000576

 Department IssuesSigned OffIntl

These plans are for a 332 head NFPA 13 Wet fire sprinkler system designed as light hazard.  The plans are REJECTED for the following reasons. 

 

The outside covered walkway indicated on the drawings is showing standard pendant heads.   Please indicated how NFPA 13 8.15.3.1.1 will be met.