These plans are for a 75 device addressable fire alarm system for the St. Johns County Fire Administration Building. The plans are APPROVED as submitted with some comments below.
|
4/26/2007
| PJW |
|
|
Please note on the plans the added eleven (11) pull stations. The plan only showed 1 pull station for the entire building. Per NFPA 72:5.12.6 pull stations are required within 5 feet of the exit doorway opening at each exit on each floor. I have indicated on the plans the locations that the pull stations are required. Note: The locations are not intended to be the exact location to mount the box but rather to indicate the exits that require them.
Also ensure that the pull station in the lobby is installed to meet the 5' requirement. On the plan it appears close.
|
4/26/2007
| PJW |
|
|
It appears to be a printing error, however please ensure that the horn strobe on the second floor is moved out of the break room into the hallway per the engineers layout.
|
4/26/2007
| PJW |
|
|
The fire alarm dedicated branch circuit and connections (breaker) shall meet the following requirements:
- It shall be mechanically protected to prevent it from being tampered. (ie/ breaker lock.)
- It shall be marked red, accessible only to authorised personnel, and shall be identified as "FIRE ALARM CIRCUIT".
- The location of the disconnecting means shall be permanently identified at the FACP.
NFPA 72 4.4.1.4.2.
|
4/26/2007
| PJW |
|
|
Ensure that the audible signals have a sound level of at least 15 db. above average ambient sound level or 5 db. above the maximum sound level having at least 60 second duration, throughout all occupiable areas. Areas in question will be verified at the time of final. NFPA 72 7.4.2.1.
|
4/26/2007
| PJW |