Plan approved for 2 exhaust hoods. This was reviewed under NFPA 96, 2001 edition.

1/19/2007 SLM
For a point of information to the General Contractor, The Fire Marshals' Office requires that a fire inspector witness a light test of the duct from the hood trough the roof, we recommend that the light test be done before the duct is raised into the ceiling. Pass this on to your mechanical contractor for the hood. 1/19/2007 SLM