Clearance Sheet C2006-002966

 Department IssuesSigned OffIntl

Plan approved for remodel of a  4137 sq ft restaurant. This was reviewed under 2004 Fl Fire Prevention Code under assembly. There is no fire alarm or sprinkler system in this bldg.

10/19/2006 SLM
The Grease Exhaust Hood and Fire Suppression System noted on this plan are conceptual. A separate permit will be required by the Fire Marshal. A HOLD will be placed on the building permit and NO INSPECTION will be done until this permit is submitted & approved. 10/19/2006 SLM
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". NFPA 1, 10.13.1.2 10/19/2006 SLM
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 10/19/2006 SLM
The occupant load shall be posted in a conspicuous place near the main entrance/exit from the room. Please refer to the Fire Marshal Notation on the plans as to the approved maximum occupant load to be posted. The Posting should read,"Maximum Occupant Load 184 Persons, by order of the Fire Marshal" 10/19/2006 SLM
Duct Smoke Detectors in a building without a fire alarm shall have a visible & audible signal locatd in normally occupied space. (NFPA 90A,4.4.4.3) 10/19/2006 SLM
The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. NFPA 101 7.2.1.3. 10/19/2006 SLM
The interior finish for this occupancy is Class A or B, Prior to final inspection please provide copies of all test documents for finishes to insure the required class. 10/19/2006 SLM