| | Department Issues | Signed Off | Intl |
|
|
Plan approved for IBO of 1400 sq ft suite of existing strip mall. This was reviewed under 2004 Fl Fire Prevention Code as new business. If there a fire alarm or fire sprinkler system, any work on these systems require a separate permit.
|
11/20/2006
| SLM |
|
|
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061)
|
11/20/2006
| SLM |
|
|
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". NFPA 1, 10.13.1.2
|
11/20/2006
| SLM |
|
|
All doors that have dead bolts shall use thumb type single cylinder.
|
11/20/2006
| SLM |
|
|
The elevation of the floor surface on both sides of a door shall not vary by more than a
1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. NFPA 101 7.2.1.3.
|
11/20/2006
| SLM |