Clearance Sheet C2006-001413*003

 Department IssuesSigned OffIntl

Plan approved for 1400 sq ft IBO of suite in existing bldg. This was reviewed under 2004 Fl Fire Prevention Code as new business. If there is a fire alarm or fire sprinkler system, any work done on these systems require separate permit.

11/20/2006 SLM
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 11/20/2006 SLM
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". NFPA 1, 10.13.1.2 11/20/2006 SLM
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required) NFPA 90A,4.4.2 11/20/2006 SLM
All doors that have dead bolts shall use thumb type single cylinder. 11/20/2006 SLM
The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. NFPA 101 7.2.1.3. 11/20/2006 SLM