These plans are for a 3 device fire alarm system intended only to monitor the sprinkler system.  The plans are APPROVED. 

7/23/2007 PJW

It was not indicated on the drawings but per a phone conversation with the contractor, the fire alarm system will dial using 2 standard telephone lines and it will have a dedicated power supply. 

7/23/2007 PJW
The fire alarm dedicated branch circuit and connections (breaker) shall meet the following requirements: - It shall be mechanically protected to prevent it from being tampered. (ie/ breaker lock.) - It shall be marked red, accessible only to authorised personnel, and shall be identified as "FIRE ALARM CIRCUIT". - The location of the disconnecting means shall be permanently identified at the FACP. (NFPA 72 4.4.1.4.2) 7/23/2007 PJW