These plans are for a 3 device fire alarm system intended only to monitor the sprinkler system. The plans are APPROVED.
|
7/23/2007
| PJW |
|
|
It was not indicated on the drawings but per a phone conversation with the contractor, the fire alarm system will dial using 2 standard telephone lines and it will have a dedicated power supply.
|
7/23/2007
| PJW |
|
|
The fire alarm dedicated branch circuit and connections (breaker) shall meet the following requirements:
- It shall be mechanically protected to prevent it from being tampered. (ie/ breaker lock.)
- It shall be marked red, accessible only to authorised personnel, and shall be identified as "FIRE ALARM CIRCUIT".
- The location of the disconnecting means shall be permanently identified at the FACP.
(NFPA 72 4.4.1.4.2)
|