| | Department Issues | Signed Off | Intl |
|
|
Plan approved for 29,620 sq ft 3 story hotel. This is reviewed using 2004 Fl Fire Prevention Code using FAC 69A-43 and new hotel chapter.
|
5/5/2006
| SLM |
|
|
The UNDERGROUND CONTRACTOR for the installation & hydro test of the fire sprinkler line will require a separate permit. A HOLD will be placed and no inspections past the slab will be done until this permit is submitted & approved.
|
5/5/2006
| SLM |
|
|
The Fire Sprinkler information provided in these plans are conceptual. A separate fire sprinkler permit is required by the Fire Marshal. A HOLD will be placed and no inspections past the slab will be done until this permit is submitted & approved. Sprinkler criteria present. This will be a NFPA 13 wet and dry system.
|
5/5/2006
| SLM |
|
|
Any reference to the Fire Alarm in these plans are conceptual. A separate permit is required by the Fire Marshal. A HOLD will be placed and no inspections past the slab will be done until this permit is submitted & approved. Fire Alarm criteria present. Fire alarm required to be monitored.
Specialized smoke dets for deaf and hearing impaired required and be at least 100 candela and be recognized for the purpose of alerting the deaf in event of a fire.
|
5/5/2006
| SLM |
|
|
Any draperies, curtains, and other loosely hanging furnishings and decorations shall be flame resistance. Documentation required at the FINAL.
|
5/5/2006
| SLM |
|
|
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061)
|
5/5/2006
| SLM |
|
|
FYI:Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6".
|
5/5/2006
| SLM |
|
|
Provide a EMERGENCY ACCESS KEY BOX near the main entrance. This box is required because there is a fire sprinkler riser located inside this building. An authorization form for the Knox Box can be obtained at the Fire Marshal's Office.(4455 Avenue "A", Suite 100, St Augustine, Phone 904-209-7400)
|
5/5/2006
| SLM |
|
|
FIRE LANES shall be marked with free standing signs with the words "NO PARKING FIRE LANE BY ORDER OF THE FIRE DEPARTMENT." Such signs shall be 12" by 18" with a white background & red letters and shall be a minimum of 7-feet in height from the roadway to the bottom part of the sign. The sign shall be within sight of the traffic flow and be a maximum of 60 feet apart.(FPC 1.3.5.4)
|
5/5/2006
| SLM |
|
|
All doors that have dead bolts shall use thumb type single cylinder. No keyed locks or special locks on doors leading to the outside.
|
5/5/2006
| SLM |