The plans are for a 90 head NFPA 13R aboveground fire sprinkler system for a 3 story Hotel.  The system is a split riser wet/dry system, the dry for the attic.  The plans are APPROVED as submitted. The underground fire main will require a seperate permit.     

 

Note: NFPA 13R does not require sprinklers in the attic, however the architect of record called for this attic to be protected anyways.