SJC Home
Clearance Sheet C2006-000750*003

 Department IssuesSigned OffIntl
These plans are a resubmittal for a 3200 square foot unsprinklered office building that will have 2 tenant spaces separated by 1 hour fire walls. Each tennant space will consist of 3 offices, a conference room, and a reception area. The 2004 Florida Fire Prevention Code business chapter was used for review. The previous comments have been addressed. The plan in APPROVED. 5/2/2006 PJW
FYI- The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. NFPA 101 7.2.1.3. 5/2/2006 PJW
FYI- All doors that have dead bolts shall use thumb type single cylinder. 5/2/2006 PJW
FYI- Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required) 5/2/2006 PJW
FYI- Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". 5/2/2006 PJW
FYI- Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 5/2/2006 PJW